Outdoor High-Voltage Vacuum Circuit Breaker ZW7-40.5

Availability:
Quantity:

The ZW7-40.5 series outdoor high-voltage vacuum circuit breakers are applied in three-phase power systems with a rated voltage of 40.5kV and a frequency of 50Hz, serving to make and break load current, overload current and short-circuit current.


1.     Ambient air temperature: Upper limit +40℃, lower limit -30℃ (general areas), -40℃ (alpine areas)

2.     Altitude: ≤1000m (If the altitude increases, the rated insulation level shall be raised accordingly)

3.     Wind pressure: ≤700Pa (equivalent to a wind speed of 34m/s)

4.     Seismic intensity: ≤8 degrees

5.     Pollution class: Class IV

6.     Maximum daily temperature difference: ≤25℃


Name

Value

Rated voltage

40.5KV

Rated Insulation Level:

1minPower Frequency Withstand Voltage (1min, Dry Test)

95kv

Power Frequency Withstand Voltage (1min, Wet Test)

80KV

Lightning Impulse Withstand Voltage (Peak)

185KV

Rated Current

1250;1600;2000A

Rated Short-Circuit Breaking Current

20 ;25; 31.5KA

Rated Operating Sequence

Open - 0.3s - Close-Open - 180s - Close-Open

Number of Rated Short-Circuit Breaking Operations

12times

Rated Short-Circuit Making Current (Peak)

50 ;63; 80KA

Rated Peak Withstand Current

Rated Short-Circuit Duration

4s

Contact Opening Stroke

22±2s

Contact Over-Travel

4±1 mm

Average Opening Speed

1.5±0.2

Average Closing Speed

0.7±0.2

Contact Closing Bounce Time

≤2

Three-Phase Opening/Closing Synchronism Deviation

≤2

Closing Time

≤150

Opening Time    

≤60

DC Resistance per Phase Circuit

≤100μΩ

Center Distance Between Phases

710mm

Allowable Wear Thickness of Moving & Fixed Contacts

3mm

Overall Dimensions (L×W×H)

2541*576*2218 mm

Mechanical Life

10000

Rated Operating Voltage & Auxiliary Circuit Rated Voltage

DC110/220 AC110/220

DC Resistance per Phase Circuit (Excluding Transformer)

≤100

Weight

800kg