EnglishThe ZW7-40.5 series outdoor high-voltage vacuum circuit breakers are applied in three-phase power systems with a rated voltage of 40.5kV and a frequency of 50Hz, serving to make and break load current, overload current and short-circuit current.
1. Ambient air temperature: Upper limit +40℃, lower limit -30℃ (general areas), -40℃ (alpine areas)
2. Altitude: ≤1000m (If the altitude increases, the rated insulation level shall be raised accordingly)
3. Wind pressure: ≤700Pa (equivalent to a wind speed of 34m/s)
4. Seismic intensity: ≤8 degrees
5. Pollution class: Class IV
6. Maximum daily temperature difference: ≤25℃
Name | Value | |
Rated voltage | 40.5KV | |
Rated Insulation Level: | 1minPower Frequency Withstand Voltage (1min, Dry Test) | 95kv |
Power Frequency Withstand Voltage (1min, Wet Test) | 80KV | |
Lightning Impulse Withstand Voltage (Peak) | 185KV | |
Rated Current | 1250;1600;2000A | |
Rated Short-Circuit Breaking Current | 20 ;25; 31.5KA | |
Rated Operating Sequence | Open - 0.3s - Close-Open - 180s - Close-Open
| |
Number of Rated Short-Circuit Breaking Operations | 12times | |
Rated Short-Circuit Making Current (Peak) | 50 ;63; 80KA | |
Rated Peak Withstand Current | ||
Rated Short-Circuit Duration | 4s | |
Contact Opening Stroke | 22±2s | |
Contact Over-Travel | 4±1 mm | |
Average Opening Speed | 1.5±0.2 | |
Average Closing Speed | 0.7±0.2 | |
Contact Closing Bounce Time | ≤2 | |
Three-Phase Opening/Closing Synchronism Deviation | ≤2 | |
Closing Time | ≤150 | |
Opening Time | ≤60 | |
DC Resistance per Phase Circuit | ≤100μΩ | |
Center Distance Between Phases | 710mm | |
Allowable Wear Thickness of Moving & Fixed Contacts | 3mm | |
Overall Dimensions (L×W×H) | 2541*576*2218 mm | |
Mechanical Life | 10000 | |
Rated Operating Voltage & Auxiliary Circuit Rated Voltage | DC110/220 AC110/220 | |
DC Resistance per Phase Circuit (Excluding Transformer) | ≤100 | |
Weight | 800kg | |