EnglishThis Automatic Transfer Switch (ATS) is applicable to three-phase four-wire dual-power supply grids with AC 50Hz, rated voltage 400V and rated current up to 3200A. It can automatically transfer one or several load circuits from one power source to the other, so as to ensure the normal power supply of the load circuits.
1. Adopt dual composite contacts, embedded mechanism, micro-motor pre-energy storage and micro-electronic control technology, basically achieving zero arcing (no arc extinguishing cover).
2. Adopt reliable mechanical interlock and electrical interlock; the executive component adopts an independent load isolation switch, ensuring safe and reliable use.
3. Adopt zero-crossing technology; in case of emergency, it can be forced to zero position (cut off both power sources at the same time) to meet the needs of fire linkage.
4. The switching of the executive load isolation switch is driven by a single motor, featuring reliable and stable switching, no noise and small impact force.
5. The drive motor of the operator only passes current at the moment of switching the executive load isolation switch; no working current is required when there is no switching, achieving significant energy saving.
6. The executive load isolation switch is equipped with a mechanical interlock device to ensure that the common and standby power sources work reliably without mutual interference.
7. It has obvious on-off position indication, padlock and other functions, reliably realizing isolation between power supply and load.
8. It has good safety performance, high automation and high reliability.
9. The product has a zero position state.
10. Easy to install; the control circuit adopts plug-in terminal connection.
11. Operation functions: manual operation and automatic control operation. Manual operation is prohibited in automatic state; if manual operation is required, the automatic electrical lock position must be turned off.
Rated Heating Current Ith | 100A | 160A | 250A | 630A | 1600A | 3200A |
Rated Insulation Voltage Ui(V) | 500V | 800V | ||||
Rated Impulse Withstand Voltage Uiimp | 6KV | 8KV | ||||
Rated Short-time Withstand Current Icw | 5kv | 10kv | 16kA | |||
Switching Operation Time | ≤3s | 5s | ||||
Power Supply Voltage Deviation | ≤85% Ue | |||||
Service Category | AC-33iB | |||||
Installation Category | Ⅱ | |||||
Pollution Degree | 3 | |||||
Control Power Supply Voltage | AC230V
| |||||
Normal Operating Conditions
1.Ambient air temperature: max. +40℃, min. -5℃; the average temperature within 24 hours shall not exceed +35℃.
2.Installation altitude: shall not exceed 2000m.
3.Relative atmospheric humidity: max. 50% at the ambient maximum temperature of +40℃, and higher humidity is allowed at lower temperatures; the average maximum relative humidity of the wettest month shall not exceed 90%, while the monthly average minimum temperature of the same month shall not exceed +25℃.
Condensation on the product surface caused by temperature changes shall be taken into account. The product shall be installed in a place free from shock, vibration, rain and snow intrusion.
4.Electrical grade: PC grade.
5.EMC equipment emission class: Environment B.
6.The product shall be handled with care and not placed upside down during transportation.