The LW-252/4000-50 type self-energy AC high-voltage sulfur hexafluoride circuit breaker is an outdoor product, applicable to the AC 50Hz power grid with a maximum voltage of 252kV in areas with an altitude not exceeding 2000m, an ambient temperature not lower than -30℃ and a pollution class not higher than Class IV. It is used to interrupt the rated current and fault current, or switch circuits, so as to realize the control and protection of the power system, and can also be used as an interconnection circuit breaker.
This product adopts SF6 gas as the arc-extinguishing and insulating medium, and uses world leading self-energy arc-extinguishing technology, equipped with a new type of spring operating mechanism. It features long electrical life, low operating work, low noise and high reliability, with a simple structure, small volume and long maintenance-free period. In the current trend of oil-free and large-capacity power equipment, it can completely replace the same type of imported products.
1. The circuit breaker adopts a three-phase porcelain-column type single-break structure, with one spring operating mechanism configured for each phase and three-phase electrical interlock, boasting a novel and exquisite appearance.
2. SF₆ gas is used as the insulating and arc-extinguishing medium for the circuit breaker, and a pointer-type density relay is adopted to monitor its pressure and density. Based on the self-energy arc-extinguishing principle and with the optimized design of the breaker's motion system, the mechanical efficiency is effectively improved and the operating work is reduced to the maximum extent.
3. Excellent breaking performance and long electrical service life.
4. Each pole of the product is mounted on a mechanism box, which is centrally installed on the foundation bolts. The box houses a spring operating mechanism and an electrical control unit, with the output rod of the mechanism connected to the crank arm. The surface of the mechanism box bracket is treated with hot-dip galvanizing process, the fasteners are hot-dip galvanized, and the shell of the mechanism box is made of stainless steel material, endowing the product with excellent corrosion resistance.
5. High mechanical reliability and capable of frequent operation.Benefiting from the inherent high insulation strength of SF₆ gas and the optimal contact movement adopted by the circuit breaker, the breaker realizes no restriking when breaking capacitive current.
6. High external insulation level with a large creepage distance design for external insulation, featuring excellent pollution resistance.High current-carrying capacity: The temperature rise test is conducted at 1.2 times the rated current of 4000A, and there is still a large margin for temperature rise at all points.
The overall product features a compact appearance and structure, facilitating on-site installation and commissioning with low maintenance workload.
Main Technical Parameters of the Mechanism
No | Name | Specification | |
1 | Auxiliary circuit voltage | DC220V, AC220V | |
2 | Opening/closing coil voltage/current | DC110/4; DC220/2.5 V/A | |
3 | Energy storage motor | Rated voltage | DC220V, AC220V |
Normal operating voltage range | 85%-110% V | ||
Power | 600W | ||
4 | Motor energy storage time | ≤15s | |
5 | Heater and lighting circuit voltage | AC220V | |
6 | Auxiliary switch rated voltage | DC220V,AC220V | |
7 | Auxiliary switch rated current | 10 | |
8 | Number of auxiliary switch contacts | 10 NO + NC | |
Main Technical Parameters of the Circuit Breaker
No | Name | Specification | ||
1 | Rated voltage | 252KV | ||
2 | Rated Power-Frequency Withstand Voltage(1min) | To ground | 460
| |
Between breaks | 460+146 | |||
Rated Lightning Impulse Withstand Voltage | To ground | 1050 | ||
Between breaks | 1050+206 | |||
3 | Rated Frequency | 50Hz | ||
4 | Rated Current | 4000A | ||
5. | First-Pole-To-Clear Factor | 1.3 | ||
6. | Rated Short-Circuit Breaking Current | 50kA | ||
7 | Peak Value of Rated Short-Circuit Making Current | 125kA | ||
8 | Rated Short-Circuit Withstand Current | 50kA | ||
9 | Rated Peak Withstand Current | 125kA | ||
10 | Rated Short-Circuit Duration | 3s | ||
11 | Rated Out-of-Step Breaking Current | 12.5KA | ||
12 | Near-Zone Fault Breaking Current | 90%IK,75%IK KA | ||
13 | Rated Line Charging Making and Breaking Current | 200A | ||
14 | Rated Operating Sequence | O-0.3S-CO180S-CO | ||
15 | Main Circuit Resistance | ≤ 55μΩ | ||
16 | Rated SF6 Gas Pressure (Gauge pressure at 20℃) | 0.6Mpa | ||
17 | Alarm / Minimum Functional Pressure (Gauge pressure at 20℃) | 0.55±0.015/0.050±0.015 | ||
18 | Annual SF6 Gas Leakage Rate | ≤0.5% | ||
19 | SF6 Gas Moisture Content (V/V) | ≤150 ppm | ||
20 | Mechanical Life | 10000times | ||
21 | Radio Interference Voltage | <500 μ∨ | ||
22 | Creepage Distance | Between breaks | ≥8660 mm | |
23 | To ground | ≥6900 mm | ||
24 | SF6 Gas Filling Weight per Unit | 24 kg | ||
25 | Weight of Each Circuit Breaker | 1500 kg | ||