EnglishEnglish
You are here: Home / Products / High-voltage Series / SF6 Circuit Breakers / Outdoor High-Voltage AC Sulfur Hexafluoride Circuit Breaker LW-252/4000-50

loading

Share to:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat sharing button
telegram sharing button
sharethis sharing button

Outdoor High-Voltage AC Sulfur Hexafluoride Circuit Breaker LW-252/4000-50

Availability:
Quantity:

The LW-252/4000-50 type self-energy AC high-voltage sulfur hexafluoride circuit breaker is an outdoor product, applicable to the AC 50Hz power grid with a maximum voltage of 252kV in areas with an altitude not exceeding 2000m, an ambient temperature not lower than -30℃ and a pollution class not higher than Class IV. It is used to interrupt the rated current and fault current, or switch circuits, so as to realize the control and protection of the power system, and can also be used as an interconnection circuit breaker.

This product adopts SF6 gas as the arc-extinguishing and insulating medium, and uses world leading self-energy arc-extinguishing technology, equipped with a new type of spring operating mechanism. It features long electrical life, low operating work, low noise and high reliability, with a simple structure, small volume and long maintenance-free period. In the current trend of oil-free and large-capacity power equipment, it can completely replace the same type of imported products.


1.     The circuit breaker adopts a three-phase porcelain-column type single-break structure, with one spring operating mechanism configured for each phase and three-phase electrical interlock, boasting a novel and exquisite appearance.

2.     SF₆ gas is used as the insulating and arc-extinguishing medium for the circuit breaker, and a pointer-type density relay is adopted to monitor its pressure and density. Based on the self-energy arc-extinguishing principle and with the optimized design of the breaker's motion system, the mechanical efficiency is effectively improved and the operating work is reduced to the maximum extent.

3.     Excellent breaking performance and long electrical service life.

4.     Each pole of the product is mounted on a mechanism box, which is centrally installed on the foundation bolts. The box houses a spring operating mechanism and an electrical control unit, with the output rod of the mechanism connected to the crank arm. The surface of the mechanism box bracket is treated with hot-dip galvanizing process, the fasteners are hot-dip galvanized, and the shell of the mechanism box is made of stainless steel material, endowing the product with excellent corrosion resistance.

5.     High mechanical reliability and capable of frequent operation.Benefiting from the inherent high insulation strength of SF₆ gas and the optimal contact movement adopted by the circuit breaker, the breaker realizes no restriking when breaking capacitive current.

6.     High external insulation level with a large creepage distance design for external insulation, featuring excellent pollution resistance.High current-carrying capacity: The temperature rise test is conducted at 1.2 times the rated current of 4000A, and there is still a large margin for temperature rise at all points.

The overall product features a compact appearance and structure, facilitating on-site installation and commissioning with low maintenance workload.


Main Technical Parameters of the Mechanism

No

Name

Specification

1

Auxiliary circuit voltage

DC220V, AC220V

2

Opening/closing coil voltage/current

DC110/4;  DC220/2.5  V/A

3

Energy storage motor

Rated voltage

DC220V, AC220V

Normal operating voltage range

85%-110% V

Power

600W

4

Motor energy storage time

≤15s

5

Heater and lighting circuit voltage

AC220V

6

Auxiliary switch rated voltage

DC220V,AC220V

7

Auxiliary switch rated current

10

8

Number of auxiliary switch contacts

10 NO + NC


Main Technical Parameters of the Circuit Breaker

No

Name

Specification

1

Rated voltage

252KV

2

Rated Power-Frequency Withstand Voltage(1min)

To ground

460

Between breaks

460+146

Rated Lightning Impulse Withstand Voltage

To ground

1050

Between breaks

1050+206

3

Rated Frequency

50Hz

4

Rated Current

4000A

5.

First-Pole-To-Clear Factor

1.3

6.

Rated Short-Circuit Breaking Current

50kA

7

Peak Value of Rated Short-Circuit Making Current

125kA

8

Rated Short-Circuit Withstand Current

50kA

9

Rated Peak Withstand Current

125kA

10

Rated Short-Circuit Duration

3s

11

Rated Out-of-Step Breaking Current

12.5KA

12

Near-Zone Fault Breaking Current

90%IK,75%IK KA

13

Rated Line Charging Making and Breaking Current

200A

14

Rated Operating Sequence

O-0.3S-CO180S-CO

15

Main Circuit Resistance

≤ 55μΩ

16

Rated SF6 Gas Pressure (Gauge pressure at 20℃)

0.6Mpa

17

Alarm / Minimum Functional Pressure (Gauge pressure at 20℃)

0.55±0.015/0.050±0.015

18

Annual SF6 Gas Leakage Rate

≤0.5%

19

SF6 Gas Moisture Content (V/V)

≤150 ppm

20

Mechanical Life

10000times

21

Radio Interference Voltage

<500 μ∨

22

Creepage Distance

Between breaks

≥8660 mm

23

To ground

≥6900 mm

24

SF6 Gas Filling Weight per Unit

24 kg

25

Weight of Each Circuit Breaker

1500 kg


Copyrights  2026 Wenzhou Holink Electirc Import&Export Co., Ltd. All Rights Reserved.  Sitemap  | Privacy Policy